Archives

  • Archives
  • >
  • Home

DOI : ,    Vol.18, No.5, 3 ~ 9, 2010
Title
A Study on the Characteristics and Configuration of Wastewater Treatment System on Tunneling Wastewater
강용태 Yong Tae Kang , 송근관 Kune Kwan Song , 한상윤 Sang Yun Han , 손정호 Jeong Ho Son , 김연은 Yun Eun Kim , 배종환 Jong Hwan Bae
Abstract
In this paper, Characteristics of Tunneling wastewater is high alkali about pH 11.25~11.85, Turbidity is experimented from 2590NTU to 413NTU. On the other hand COD(Mn). T-N, T-P is very lower than Permissible discharge standards due to make almost particle. the optimum dosage of flocculant for tunneling wastewater with pH and turbiditiy changes. The samples were mixed rapidly(200rpm-3min) and mixed slowly (30rpm-30min), then settled(10min). The optimum dosage of aluminum sulfate is 20ml/L and Polymer is 0.4m1/L even pH changes and turbidity changes. As a result, pH changes and turbidity changes have not decisive effect on treatment water quility. Also, 바이오큐브 media is the best removal efficiency on sample 1 than other medias, The removal efficiency of particle in 바이오큐브 media on sample2 is 88% for 30min. More filtration studies of tunneling wastewater must be done.
Key Words
Tunneling wastewater, Filtration, Jar-test, Turbidity, pH
pdf view PDF